Fire Sprinkler Systems

About Connecticut Fire Equipment, Inc.

Fire sprinkler systems have been the most effective form of fire protection for decades, but they must be inspected, tested and maintained in accordance with the requirements of the National Fire Protection Association and the Authority Having Jurisdiction.

Fire sprinkler systems are required to be inspected in accordance with NFPA 25. Our highly trained technicians can inspect, service, repair and install all types of sprinkler systems. Our compliance tracking system will keep a record of when inspections are due so you never have to worry about being delinquent on required inspections. We will call you! Connecticut Fire Equipment, Inc. will keep all report documentation on file and readily available to you and your approving agency, as well as left on–site. We can also provide training in the proper use and maintenance of your system so in a fire situation everyone will be prepared to respond appropriately.

Fire SpinklerInspections are performed using Connecticut Fire Equipment, Inc. technicians, without sub-contracting. We do not depend on another company for expertise we use our own technicians to inspect your fire sprinkler system; this gives us better control over the quality of service we are able to provide. When you call Connecticut Fire Equipment, Inc. we put you in contact with an individual specifically trained to address your fire protection needs.


Sprinkler Service With Fire Alarm Service

Chances are your building has not just a fire sprinkler system, but a building fire alarm system as well. The two systems are almost always connected. Connecticut Fire Equipment, Inc. has the ability to inspect both systems in accordance with applicable NFPA codes. Meet and schedule with one company! We can work with your facility manager to maximize efficiency. When services are scheduled together it means less visits and more time for your facility management team to focus on other areas demanding their attention. Many times a facility will have to coordinate scheduling with different vendors to complete all of the necessary inspections, repairs and maintenances due for different services. Connecticut Fire Equipment, Inc. has the solution…we will send certified and professional technicians for each service, our goal is to complete these inspections in one convenient visit! We take care of all the compliance tracking and call you when service or maintenance is due, without the need for follow-up by the customer. When different vendors handle and service different areas, most times the communication between the service companies is non-existent. Having one company to handle all of the fire protection services provides you with the confidence that all areas are in compliance and working together to create the safest environment possible.


Fire Sprinkler Pump »back to top

Fire PumpFire pumps are often a forgotten element of an automatic fire protection system. If a fire pump does not work, the entire system may fail. Stringent inspection and te sting requirements are intended to prevent a pump failure that could be catastrophic. All functions of the fire pump controller should also be tested at least annually. Call Connecticut Fire Equipment, Inc. today for inspections, testing, installation and repairs.


Fire Sprinkler Backflow Preventer »back to top

Fire Sprinkler Back Flow PreventerA fire sprinkler backflow preventer is a device that prevents backflow through a cross connection. Backflow is the undesirable reversal of flow of water or other substances through a cross connection into the public water system or the consumers potable water system. The state of Connecticut Department of Public Health requires all testable backflow preventers are to be tested soon after installation and at no more than twelve month intervals after that. Call Connecticut Fire Equipment, Inc. today for inspections, testing, installation and repairs.

Please contact us today for more information!»back to top

Sprinkler Systems Monthly Quarterly Semi-annual Annual Other Code NFPA 10
INSPECTION
Gauges - Dry, PreAction & Deluge         Check Box 2-2.4.2 Gauges on dry, preaction, and deluge systems shall be inspected weekly to ensure that normal air and water pressures are being maintained.
Gauges - Wet Pipe Systems Check Box         2-2.4.1 Gauges on wet pipe sprinkler systems shall be inspected monthly to ensure that they are in good condition and that normal water supply pressure is being maintained.
Control Valves Check Box       Check Box   (See "Valves" below)
Alarm Devices   Check Box       2-2.6 Alarm devices shall be inspected quarterly to verify that they are free of physical damage.
Hydraulic Nameplate   Check Box       2-2.7 The hydraulic nameplate, if provided, shall be inspected quarterly to verify that it is attached securely to the sprinkler riser and is legible.
Buildings       Check Box   2-2.5 Annually, prior to the onset of freezing weather, buildings with wet pipe systems shall be inspected to verify that windows, skylights, doors, ventilators, other openings and closures, blind spaces, unused attics, stair towers, roof houses, and low spaces
Hangers/Bracing       Check Box   2-2.3 Sprinkler pipe hangers and seismic braces shall be inspected annually from the floor level.
Pipe & Fittings       Check Box   2-2.2 Sprinkler pipe and fittings shall be inspected annually from the floor level.
Sprinkler Heads       Check Box   2-2.1.1 Sprinklers shall be inspected from the floor level annually.
Spare Sprinkler Heads       Check Box   2-2.1.3 The supply of spare sprinklers shall be inspected annually…
Valves (All Types)             (See "Valves" below)
TESTING
Alarm Devices   Check Box       2-3.2 Waterflow alarm devices including, but not limited to, mechanical water motor gongs, vane-type waterflow devices, and pressure switches that provide audible or visual signals shall be tested quarterly.
Main Drain   Check Box         (See "Valves" below)
Antifreeze Solution       Check Box   2-3.4 The freezing point of solutions in antifreeze shall be tested annually by measuring the specific gravity with a hydrometer or refractometer and adjusting the solutions if necessary.
Gauges         Check Box 2-3.2 Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced.
Sprinkler Heads         Check Box 2-3.1.1 Where sprinklers have been in service for 50 years, they shall be replaced or representative samples from one or more sample areas shall be submitted to a recognized testing laboratory acceptable to the authority having jurisdiction for field service test
Sprinkler Heads - Extra High Temp         Check Box 2-3.1.1 Exception No. 3*: Representative samples of solder-type sprinklers with a temperature classification of extra high [325°F (163°C)] or greater that are exposed to semi continuous to continuous maximum allowable ambient temperature conditions shall be tested
Sprinkler Heads - Fast Response         Check Box 2-3.1.1 Exception No. 2: Sprinklers manufactured using fast response elements that have been in service for 20 years shall be tested. They shall be retested at 10-year intervals.
MAINTENANCE
Valves (All Types)       Check Box Check Box   (See "Valves" below)
Obstruction Investigation         Check Box 10-2.2 Systems shall be examined internally for obstructions where conditions exist that could cause obstructed piping. If the condition has not been corrected or the condition is one that could result in obstruction of piping despite any previous flushing procedures.
Valves Monthly Quarterly Semi-annual Annual Other Code NFPA 10
INSPECTION
Control Valves         Check Box 9-3.3.1 All valves shall be inspected weekly.
Alarm Valves Check Box         9-4.1.1 Alarm valves shall be externally inspected monthly.
Check Valves         Check Box 9-4.2.1 Valves shall be inspected internally every 5 years to verify that all components operate properly, move freely, and are in good condition.
Preaction/Deluge Valves       Check Box   9-4.3.1.3 The interior of the preaction or deluge valve and the condition of detection devices shall be inspected annually when the trip test is conducted.
Dry Pipe Valves/Quick Opening Devices       Check Box   9-4.4.1.4 The interior of the dry pipe valve shall be inspected annually when the trip test is conducted.
Backflow Prevention Assemblies       Check Box   9-6.1.2 All backflow preventers installed in fire protection system piping shall be tested annually…
TESTING
Main Drain   Check Box       9-2.6 A main drain test shall be conducted quarterly at each water-based fire protection system riser to determine whether there has been a change in the condition of the water supply piping and control valves.
Waterflow Alarm   Check Box       9-2.7 All waterflow alarms shall be tested quarterly in accordance with the manufacturer's instructions.
Control Valves       Check Box   9-3.4.1 Each control valve shall be operated annually through its full range and returned to its normal position.
Preaction/Deluge Valves       Check Box   9-4.3.2.2 Each deluge or preaction valve shall be trip tested annually at full flow in warm weather and in accordance with the manufacturer's instructions.
Dry Pipe Valves/Quick Opening Devices       Check Box   9-4.4.2.1 Each dry pipe valve shall be trip tested annually during warm weather.
Backflow Prevention Assemblies           9-6.2.1 All backflow preventers installed in fire protection system piping shall be tested annually…
MAINTENANCE
Control Valves       Check Box   9-3.5 The operating stems of outside screw and yoke valves shall be lubricated annually.
Preaction/Deluge Valves       Check Box   9-4.3.3.2 During the annual trip test, the interior of the preaction or deluge valve shall be cleaned thoroughly and the parts replaced or repaired as necessary.
Dry Pipe Valves/Quick Opening Devices           9-4.4.3.2 During the annual trip test, the interior of the dry pipe valve shall be cleaned thoroughly and parts replaced or repaired as necessary.

CT License #F-30031
MACR #004687
RI License #12-32-A3-PM
DOT Cert #C-104
Dun Bradstreet #144-769-464
Connecticut Fire Equipment, Inc.
is a proud member of:
CT Fire Equipemnet is a proud member of VFPA and NEFED
Connecticut Fire Equipment, Inc. celebrates over 30 years of excellence
Connecticut Fire Equipment, Inc.
is a proud member of:
CT Fire Equipemnet is a proud member of VFPA and NEFED